ZM-GCT Series current Transformer Used for Relay Protection

Structural parameter

                Front view                                                             Bottom view

Circuit schematic

The main technical parameters

Model

Rated

input current(A)

Rated

output voltage(V)

Accuracy class

Phase

 angle error

Overload multiples

Compressive strength(V)

remark

 ZM-GCT 1A/3.53V

1

3.53

0.1

≤5'

2

3000

measurement

 

 ZM-GCT 2A/3.53V

2

3.53

0.1

≤5'

2

 ZM-GCT 6A/1.414V

5

1.178

0.1

≤5'

2

 ZM-GCT 6A/2.4V

5

2.0

0.1

≤5'

2

 ZM-GCT 6A/3.53V

5

2.941

0.1

≤5'

2

 ZM-GCT 20A/1.414V

1

0.0707

0.2

≤20'

20

3000

protection

 ZM-GCT 20A/2.4V

1

0.12

0.2

≤20'

20

 ZM-GCT 20A/3.53V

1

0.1765

0.2

≤20'

20

 ZM-GCT 100A/1.414V

5

0.0707

0.2

≤20'

20

 ZM-GCT 100A/2.4V

5

0.12

0.2

≤20'

20

 ZM-GCT 100A/3.53V

5

0.1765

0.2

≤20'

20

 

Note: the table is commonly used models of customers, if customers require different ratios; you only need to provide the technical requirements for the design and production.


Product Inquiry

ZM-RPT Series voltage Transformer Used for Relay Protection

ZM-RCT Series current Transformer Used for Relay Protection

ZM-PT Series voltage Transformer Used for Relay Protection

ZM-CT Series current Transformer Used for Relay Protection

ZM-BPT Series Voltage Transformer Used for Relay Protection